14 Parameter reference
14.3 Parameters of the communication module for slot MXI2
108
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C14879
C14880
C14881
C14882
Parameter | Name:
C14879 | Bus error
Data type: UNSIGNED_32
Index: 9696 = 0x25E0
Display of the error currently detected on the fieldbus.
Display range (min. value | unit | max. value)
0 4294967295
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Value Meaning
0No error
3481402629 The PROFINET communication link has been interrupted.
Parameter | Name:
C14880 | Reaction on communication fault
Data type: UNSIGNED_8
Index: 9695 = 0x25DF
The action set in subcode 1 is executed when the node detects that it is no longer in the "Data_Exchange" state.
• Please also observe the notes provided in code C14881
.
• A change in the monitoring response becomes immediately effective.
Interruption of PROFINET communication
( 77)
Selection list
0 No response
1Fault
3 Quick stop by trouble
4 Warning Locked
6 Information
Subcodes Lenze setting Info
C14880/1 0: No Response
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14881 | Response time when exiting "Data_Exchange"
Data type: UNSIGNED_16
Index: 9694 = 0x25DE
If the "Data_Exchange" status is exited, the response parameterised in C14880 is activated after the time set here
has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change in the monitoring response becomes immediately effective.
Setting range (min. value | unit | max. value) Lenze setting
0 ms 65535 0ms
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C14882 | Display: Monit. time: Watchdog
Data type: UNSIGNED_32
Index: 9693 = 0x25DD
Display of the watchdog monitoring time specified by the IO controller
Note: This code will not be supported anymore from SW version 2.10 for reasons related to the system.
Display range (min. value | unit | max. value)
0 4294967295
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT