14 Parameter reference
14.2 Parameters of the communication module for slot MXI1
96
Lenze · E94AYCER communication module (PROFINET®) · Communication Manual · DMS 11.0 EN · 04/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C13852
C13853
C13860
Parameter | Name:
C13852 | All words to standard device
Data type: UNSIGNED_16
Index: 10723 = 0x29E3
Display of the process data words 1 ... 32 that are transmitted from the communication module to the inverter.
Display range (min. value | unit | max. value)
0 65535
Subcodes Info
C13852/1
...
C13852/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13853 | All words from standard device
Data type: UNSIGNED_16
Index: 10722 = 0x29E2
Display of the process data words 1 ... 32 that are transmitted from the inverter to the communication module.
Display range (min. value | unit | max. value)
0 65535
Subcodes Info
C13853/1
...
C13853/32
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13860 | Settings
Data type: UNSIGNED_8
Index: 10715 = 0x29DB
From SW version 3.00 onwards
Display of current configuration data
Display range (min. value | unit | max. value)
0 255
Subcodes Info
C13860/1 PROFIsafe
•0: not active
•1: active
C13860/2 Number of process data words
C13860/3 Reserved
C13860/4 Number of PROFIsafe words (0, 4 or 8 words)
Read access Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT