CMVETH01B 58
Reference
No Name Access Default Possible Settings Comments
426 TTL Value R/W 1 1 minimum
255 maximum
Time-to-live value for IP multicast packets
427 Configuration Control R/W 0 0 – stored
1 - DHCP
Source of configuration values
428 Duplex Control R/W 1 0 – half duplex
1 – full duplex
429 Interface Speed Control R/W 1 0 – 10Mbps
1 - 100Mbps
430 Interface Speed Actual RO 100 – 100Mbps
10 - 10Mbps
431 NetIdleMode
(Idle event received in I/O
message header)
R/W 0 0 – Network Fault 'F.nF1'
1 – Ignore Fault Condition
2 – Vendor specific (switch off network control and
reference - no drive fault or stop!)
Mode on reception of CIP communication IDLE event
*Only active in Drive Network Control (n.xxx)
432 NetFaultMode
(Loss of I/O connection Exclusive
Owner)
R/W 0 0 – Network Fault 'F.nF2' or 'F.nF7'
1 – Ignore Fault Condition
2 – Vendor specific (switch off network control and
reference - no drive fault or stop!)
Action on loss of CIP network I/O - expected packet timeout. Timeout
period = 4*Expected packet rate (Requested Packet Interval, RPI)
or
Expiration of overall I/O message timer 'F.nF7'. The timeout value for
'overall I/O message timer is set by P435.
*Armed after at least 1 successful reception of I/O message.
*Only active in Drive Network Control (n.xxx)
433 Explicit message timeout reaction R/W 1 0 – Network Fault 'F.nF4' or 'F.nF6'
1 – Ignore Fault Condition
2 – Vendor specific (switch off network control and
reference - no drive fault or stop!)
3 – Trigger drive STOP (type set by P111)
4 – Trigger inhibit the drive (Coast to Stop)
5 – Trigger Quick Stop
Triggered by Explicit message expected packet rate time-out, 'F.nF4'
or
Expiration of overall explicit message timer 'F.nF6'. The timeout value
for 'overall explicit message timer' is set by P435.
*Armed after at least 1 successful reception of explicit message.
*Only active in Drive Network Control (n.xxx)
434 Action on overall Ethernet
timeout
(no explicit or I/O messages
received or Web Server access)
R/W 1 0 – Network Fault 'F.nF5'
1 – Ignore Fault Condition
2 – Vendor specific (switch off network control and
reference - no drive fault or stop!)
3 – Trigger drive STOP (type set by P111)
4 – Trigger inhibit the drive (Coast to Stop)
5 – Trigger Quick Stop
Trigger by expiration of timer monitoring all messages received by the
module (P435 for setup)
*Armed after at least 1 successful reception of any message
addressed to this module.
435 Message timeout – monitoring
time
R/W 2000 0 – 65535 [ms] Parameter used to monitor all explicit and I/O messages received by
the module
436 Network Status RO 4 Digit Power, Control and Network Status
Digit 1: Power Status
Digit 2: Control Status RO 0…3 0 – Local Control and reference
1 – Network Control, Local reference
2 – Local Control, Network reference
3 – Network Control, Network reference
Digit 3: Network Status 0 0 – Network not connected
1 – Network connected
Digit 4: Reserved
437 Frames Transmitted OK RO 0
438 Frames Received OK RO 0
439 Collision Count RO 0
440 Par. ID of word 0 Output R/W 2 0…9 0 – Disabled / Not evaluated
1 – SMV Control Word
2 – Network Command Frequency
3 – Lenze C135 Control Word
4 – Network Speed in unsigned RPM
5 – Network PID Setpoint
6 – Network Torque Setpoint
7 – Network Speed in signed RPM (control direction)
8 – Digital Outputs
9 – Analog Output
441 Par. ID of word 1 Output R/W 0 0…9
442 Par. ID of word 2 Output R/W 0 0…9
443 Par. ID of word 3 Output R/W 0 0…9
448 Last Accessed Output Assembly RO 1 20, 21, 100 etc.
449 Output Assembly Access Counter RO 1 0…9999 Overflow above 9999 to 0
450 Par. ID of word 0 - Input R/W 1 0…550
451 Par. ID of word 1 – Input R/W 2 0…550
452 Par. ID of word 2 – Input R/W 0 0…550
453 Par. ID of word 3 - Input R/W 0 0…550
458 Last Accessed Input Assembly RO 1 70, 71, 101 etc
459 Input Assembly Access Counter RO 1 0…9999 Overflow above 9999 to 0