Technical data
Rated data
2
EDK71MMXXX-020 DE/EN/FR 1.0
13
L
Thermal monitoring 10.
According to DIN EN 60947-4-2 (semiconductor motor control devices and starters for AC voltage)
If the motor current is x-times
... the starttec will switch off
... with an activation
higher than the output current
set under C0120 ...
within T Criteria
class set under C0121
0
105 % T=2h No activation when being
cold
–
120 % T=2h Assuming the final
temperature
0 and an
increase of the current to
120 %, it will be activated
–
150 %
T=2min
Assuming the final
Class 10A
T=4min
temperature and 100 %
Class 10
T=8min
ou
pu
cu
en
,
w
e
activated
Class 20
T=12min
Class 30
7.2-fach
max. to 9.5 A 2s< T ≤ 10 s
No activation when being
Class 10A
max.to9.0A 4s<T ≤ 10 s
cold
Class 10
max.to8.0A 6s< T ≤ 20 s Class 20
max.to7.0A 9s< T ≤ 30 s Class 30
800 % T=20ms Fixedswitchoff –
Tip!
Independently of the activation class set, the starttec will switch off after 20 ms if the motor
current is 800 % higher than the rated current set under C0120.