39
Function
Product
Description Option
Air
Conditioner
Ventilation
Fixed Air
Volume
A function to set the air volume mode
of the indoor unit to be variable / xed.
Variable: When the Comp is ON, it operates
in the set fan speed. Operate to
low fan speed at COMP OFF.
Fixed: When the Comp is ON, it operates in
the set fan speed. Operate to set fan
speed at COMP OFF.
Zone Type
A function to set the zone type
supported by the indoor unit such as
the “new” and the “old” types.
Old: You can check only the operation
status of the relevant zone by using the
wired remote controller.
New of 8 Zone: You can control and monitor
the zones by using the
wired remote controller.
Zone Number
A function to set the number of zones.
It is available only when the zone type
is “New.”
2 ~ 8
Over Heating
Control the heating thermal ON / OFF
temperature conditions.
Caution: If you incorrectly set it, it
may cause overheating or
weak heating.
Thermal On Thermal Off
Step 0
Operates in accordance with
the product set value
Step 1 4 °C (8 °F)
6 °C
(12 °F)
Step 2 2 °C (4 °F) 4 °C (8 °F)
Step 3 -1 °C (-2 °F) 1 °C (2 °F)
Step 4
-0.5 °C
(-1 °F)
0.5 °C
(1 °F)
Pipe
Temperature
You can check the temperature of the
pipe connected to the product.
-
Emergency
Heater
A function to determine whether to use
the emergency heater control function
and set the usage environment.
Enabled / Disabled