48 Chapter 6 System Operation And Maintenance
Liebert CRV+ Series Air Conditioner User Manual
Note
1. Replacing the compressor must be carried out by professional personnel, if necessary, please contact Emerson technical
support engineer.
2. The damage to the compressor components due to improper way of cleaning is classified in the warranty agreement as
improper usage of the product, thus is not covered by the warranty.
When the compressor is entirely burned, you need to replace the filter drier together with the compressor. In addition,
check the expansion valve. If the valve is faulty, replace it too. Before the replacement, you must clean the system. If
you are unsure about the cleaning method, please consult with Emerson service personnel.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert CRV+ Series and is the answer not in the manual?

Liebert CRV+ Series Specifications

General IconGeneral
RefrigerantR410A
Frequency50/60 Hz
Operating Ambient Temperature64° to 113°F (18° to 45°C)
Sound Pressure LevelVaries by model (typically 45 dB(A) to 65 dB(A))
DimensionsVaries by model (consult specific model documentation)
WeightVaries by model (consult specific model documentation)