8 Chapter 2 Mechanical Installation
Liebert CRV+ Series Air Conditioner User Manual
Note
1. When the condenser is installed higher than the compressor (see Figure 2-6), a back bend should be fitted on the discharge pipe
and liquid pipe of the condenser, to avoid refluence of liquid refrigerant upon stopping.
2. When installing the back bend, ensure that the top end of the back bend is installed higher than the highest copper pipe of the
condenser.
Back bend (must be higher than the
highest copper pipe of the condenser)
Heat insulation floor Floor
Sealed
Raised floor
Humidifier
water in
Condensed
water out
Indoor unit
Liquid line (avoid exposure to direct sunlight)
Trap
Slope discharge
Max. 7.5m
Max. 30m
Outdoor unit
Figure 2-6 Condenser installed higher than compressor
Heat insulation floor
Floor
Sealed
Raised floor
Humidifier
water in
Condensed
water out
Indoor unit
Slope liquid
Min. 8m
Slope
discharge
Outdoor unit
Figure 2-7 Compressor installed higher than condenser
2.3.3 Mechanical Parameters
Indoor unit
The mechanical parameters of the indoor unit are shown in Figure 2-8 and Table 2-1.