60 Appendix 4 Parameter Setting Table
Liebert CRV+ Series Air Conditioner User Manual
Menu Parameter Default Setting range
System
Set
Fan Set
Std CFC 100% 85 ~ 100%
Hum Speed 75% 50 ~ 100%
Min Step 0.1%/s 0.1 ~ 2/s
Max Step 1.0%/s 1.0 ~ 5.0/s
Start Dly 10s 10 ~ 600s
Stop Dly 30s 10 ~ 300s
Decel Dly 5s 0 ~ 300s
LP Max 5.8Bar 5.8 ~ 7.0Bar
LP Cur 7.5Bar 6.0 ~ 8.0Bar
HP Cur 11.5Bar 10.0 ~ 20.0Bar
HP Min 13.5Bar 10.0 ~ 20.0Bar
Comp Set
Min Cap 23% 23 ~ 50%
Std Cap 100% 50 ~ 100%
Max Cap
125%/110%
(25kW/35kW)
100% ~ 125%/100% ~ 110%
(25kW/35kW)
Start Cap 70% 40 ~ 80%
Output DB 2.8% 0 ~ 5.6%
Start Rqt 50% 1% ~ 100%
Stop Rqt -150% -200% ~ -50%
WSK Period 180s 120s ~ 300s
Min Run 10min 0 ~ 30min
Min Stop 2min 0 ~ 10min
M.C Run 120min 0 ~ 120min
O.R Cap 70% 60% ~ 80%
O.R Cyc 240min 30min ~ 300min
O.R Run 5min 0 ~ 10min
LP Min 5.8Bar 5.8Bar ~ 7.0Bar
LP Cur 7.5Bar 6.0Bar ~ 8.0Bar
HP Cur 11.5Bar 10.0Bar ~ 20.0Bar
HP Max 13.5Bar 10.0Bar ~ 20.0Bar
EEV Set
SH Stpt 15.0°C 5.0°C ~ 20.0°C
SH Close 8.0°C 5.0°C ~ 10.0°C
MOP 11.0Bar 10.5Bar ~ 15.0Bar
Start OD 65% 0 ~ 100%
Start Time 60s 0s ~ 300s
Cont Time 60s 15s ~ 600s
Teamwork Set
Sys Mode SIGL SIGL, TEAM
Team Add 1 0 ~ 254
Team Num 1 1 ~ 32
Bkup Num 0 0 ~ (unit number - 1)
Rt Num 0
0 ~ smaller value in running
number and backup value
Rt Period NO NO, 1D, 2D, 3D, 4D, 5D, 6D, 7D
Rt At 12:00 0:00 ~ 23:00 (on the hour)
Manual Mode
Manual Ena No No, YES
Fan Speed 0% 0 ~ 100%
Fan Output OFF OFF, ON
Comp Cap 0%
0 ~ 125%/0 ~ 110%
(25kW/35kW)
Comp Output OFF OFF, ON
Vacuue State No No, YES
Lqiud Valve OFF OFF, ON
Heat Output OFF OFF, ON
Humd Output OFF OFF, ON
Pump Output OFF OFF, ON
Comm Alm OFF OFF, ON
Sel Option
Pump Conf No No, YES
Rem Tem Num 0 0 ~ 10
Adj R.T1 0.0°C -10.0°C ~ 10.0°C