To Add Loads to a Schedule
When you have completed programming a time
schedule, the next step is to add the loads to be
controlled.
To save the schedule press EXIT. TAB to “yes” 1.
and ENTER to save the schedule. The clock will
take a second to save the changes and exit back
to the SCHEDULE LIST menu.
TAB to “NO LOADS” and ENTER to add loads 2.
to the schedule.
Schedule 1 is
programmed and has
no loads
Schedule 3 is not
programmed
Schedule 4 is
programmed and
controls GROUP 4
Schedule 6 is
programmed, but is
disabled
SCHEDULES PAGE 1-6
Name: SCHEDULE 1
SCH 1 ==> NO LOADS
SCH 2 UNUSED
SCH 3 UNUSED
SCH 4 ==> GROUP 4
SCH 5 UNUSED
SCH 6 ==> DISABLED
TAB to MAINTAIN and SCROLL to choose the 3.
Group Type.
Quick Tip: Choose MAINTAIN for outdoor lighting
and MNTN + BLINK for indoor lighting. For a more
complete understanding of Group Types, refer to the
Group Section later in this manual.
GROUP1 MAINTAIN
EDIT: LCP-2 LOAD-5
LCP1:1-5
LCP2:3,4
Choices are
MAINTAIN•
MNTN + TIMER•
MNTN + BLINK•
TAB to LOAD 1.4.
SCROLL to the desired Load (relay) and ENTER 5.
to add to the Load Summary.
Repeat the TAB and SCROLL sequence and add 6.
as many loads as required.
GROUP1 MAINTAIN
EDIT: LCP-2 LOAD- 5
LCP1:1-5
LCP2:3,4
LCP1: 1-5 and LCP
3,4 are in the Load
Summary
Additional steps for MAINTAIN + TIMER and
MAINTAIN + BLINK Groups
These steps are considered best practice for indoor
lighting, and include after-hours relay timers.
MAINTAIN groups can EXIT at this point.
With “MNTN + __” highlighted, ENTER to set 7.
advanced options.
TAB to AUTOMATIC ON. SCROLL to change 8.
to NO AUTOMATIC ON if desired. NO
AUTOMATIC ON means lighting will not
automatically be switched on in the morning by
the clock but must be manually switched on by
an occupant. This is considered an energy savings
feature. AUTOMATIC ON will turn the lights
on by the clock, whether occupants are present
or not.
GROUP1 PARAMETERS
AUTOMATIC ON
SET TIMER
TAB to SET TIMER and ENTER to program 9.
the after-hours relay timers. This features allows
occupants to switch lights on after the scheduled
time, but only for a timed duration. This is an
energy savings feature and is required by most
energy codes.
TAB to the Hours/Minutes/Seconds display 10.
and TAB/SCROLL to set the Hours/Minutes
and Seconds of the after-hours timer. 2:00:00 is