THE BLUE BOX LT PROGRAMMING 79
LCDBBP03Sept08
TAB to “+ 0 mins”.1.
SCROLL up or down to select.2.
ON DUSK -30mins
OFF DAWN +30mins
30 mins. before dusk
30 mins. after dawn
No (NONE) Scheduled Event
In some cases you may desire that nothing at all
happen (e.g. no “off time”). In our schedule, this
Scheduled Event is referred to as “NONE”.
NONE is usually used to disable a specific day or set
of days (i.e. Sunday).
SCROLL to select NONE.1.
ON NONE
OFF NONE
Photocell Scheduled Events
A photocell connected directly to the photocell
input of the Master Blue Box LT, controls relays
only through any of the first 8 time schedules. Each
Schedule may have a unique trigger level, and may
be applied to any relay(s) in any panel(s), creating a
global photocell.
Refer to “Programming a Blue Box LT Photocell” for
programming details.
Mixing Scheduled Events - Custom Schedules
Mix up “on” and “off
events to create a
truly unique schedule..
SCH 1 EXCEPT NONE
MONDAY - FRIDAY
ON TIME: DUSK -30mins
OFF TIME: 10:00 PM
SAT ON TIME: DUSK -30mins
OFF TIME: 08:00 PM
SUN ON TIME: NONE
OFF TIME: NONE
All of the different Scheduled Events (except PCELL)
may be mixed with each other to create a variety of
scheduling options. If you need help with a particular
scheduling requirement, and do not see what you
need here, contact Technical Support, and they will
assist you.
Control Types
“Control Types” describes how loads are controlled by
schedules, switches, photocells, or DI Cards (via contact
closure switches). When controlling more than 8 relays
or when any time schedule is used, “Groups” must be
used and the Toggle feature is not available.
TOGGLE A momentary contact will toggle up to
8 loads on or off.
ON MODE A momentary contact will issue an “on”
command to as many as 8 loads.
OFF MODE A momentary contact will issue an “off
command to as many as 8 loads.
MIXED
MODE
A momentary contact will switch one
set of loads “on” and another set of
loads “off at the same time.
MAINTAIN Loads are ON for the duration of a
closure and OFF when the closure
is opened. Similar to the way a wall
switch makes and then breaks a circuit
to turn lights on or off.
Photosensor Card Triggers are usually
programmed as maintain, as is any
maintained contact closure device such
as a wall switch or a relay closure from
(for instance) a security system.
GROUPs
(1-32)
To control more than 8 loads, or when
programming a time schedule, always
use GROUPs.
Last Input Override
Your digital lighting controls use a logic structure
called “last input override” and as such, other inputs
can affect the loads too. Example: A load is toggled
on from one location and then switched off by a

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lighting Controls Blue Box LT Series and is the answer not in the manual?

Lighting Controls Blue Box LT Series Specifications

General IconGeneral
BrandLighting Controls
ModelBlue Box LT Series
CategoryController
LanguageEnglish