84 THE BLUE BOX LT PROGRAMMING
LCDBBP03Sept08
indication that the lights are in Blink Time OUT.
Where are the two locations on the DTC that a :Q
relay timer can be viewed or programmed?
USER MENU > GROUP LOADS > TAB :A
to GROUP > ENTER to select >TAB to
MAINTAIN+TIMER or MAINTAIN+BLINK
>ENTER to select >.
USER MENU >SETUP MENU >SYSTEM
RESTRICTED (PASSCODE 900001) >RELAY
PROPERTIES >select BOARD >.
You create a new MAINTAIN group or add new :Q
relays to an existing MAINTAIN group and EXIT.
Upon re-entering the group, you notice it has
changed itself into MAINTAIN+TIMER. Why?
One or more of the relays in the group :A
are also in another MAINTAIN+TIMER or
MAINTAIN+BLINK group which has assigned
it or them a timer value. Since the timer value
is written into the relay properties, it is carried
over into the new MAINTAIN group.
What does MAINTAIN mean in reference to a :Q
wall switch?
It means that the switch concerned is a contact :A
closure switch like an ordinary wall switch. When
one flips the switch UP the contacts close and
stay closed and the lights come ON. (They are
MAINTAINED that way.) When one flips the
switch down the contacts open and the lights
go off. Note that both making the circuit and
breaking the circuit (from the switch to the
contact input) causes the relay(s) to react.
What does MOMENTARY mean in reference :Q
to a switch?
It means that it is expecting a pulse as would be :A
received from a push button. The command is
executed on contact closure. The contact opening
does nothing.
How do you find out which group(s) a relay is in?:Q
Look in the “What & When Menu”: SETUP :A
MENU >SYSTEM SETUP MENU >WHAT
AND WHEN? >WHAT CONTROLS RELAYS.
Select the relay and press ENTER. Any groups
that the relay is in will be displayed.
How do you find out what is turning a group :Q
off or on?
Look in the “What & When Menu”: SETUP :A
>SYSTEM SETUP >WHAT AND WHEN?
>WHAT CONTROLS GROUPS. Select
the group and press ENTER. Any schedules,
photocells or switches that control that group
will be displayed.
What do you do to sync up the relays in a group, :Q
when some of them are on and some are off?
Go to the “group loads” screen and turn on :A
the group again using the SCROLL UP button.
If the group is already “ON” scrolling up will re-
reiterate the “ON” command.
How do you get rid of a group you don’t want :Q
to use anymore?
Go to the “GROUP LOADS” screen, highlight :A
the group and press the DELETE button.
What should you suspect is happening when you :Q
delete a group but the relays still have a timer?
Those relays are in another MAINTAIN+TIMER :A
or MAINTAIN+BLINK group which is forcing a
timer onto them.
What should you be careful never to do with :Q
MAINTAIN + TIMER or MAINTAIN + BLINK
groups?
Never have the same relay in more than one :A
MAINTAIN + TIMER or MAINTAIN + BLINK
group.
What does the “NO AUTOMATIC ON” setting :Q
in a MAINTAIN+TIMER or MAINTAIN+BLINK

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lighting Controls Blue Box LT Series and is the answer not in the manual?

Lighting Controls Blue Box LT Series Specifications

General IconGeneral
BrandLighting Controls
ModelBlue Box LT Series
CategoryController
LanguageEnglish