EasyManua.ls Logo

Logic DLC NET Series

Logic DLC NET Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
USE AND MAINTENANCE MANUAL DLC
NET
Series
Installation
LOGIC S.r.l. - M0145Db.docx
Mod. L0006A01 of 30/05/2016
Page 31 of 78
Figure 21. External buttons connection from active source
3.8.3 Connection to
setpoint output
In setpoint mode (in the menu is selected ), the
instrument activates four alarm outputs that are activated depending on the
setpoint chosen in the menu and at the intervention mode chosen (high
or low) in .
Connections are described in Table 14 and Figure 22.
It is necessary the expansion board -EB.
Table 14. Connection to setpoint output
Pin on DLC
NET
Description
TB6-1
0 Vdc
TB6-2
Out 1 (+24 Vdc transistor open-collector PNP), setpoint 1
TB6-10
Out 2 (+24 Vdc transistor open-collector PNP), setpoint 2
TB6-3
Out 3 (+24 Vdc transistor open-collector PNP), setpoint 3
TB6-11
Out 4 (+24 Vdc transistor open-collector PNP), setpoint 4
Figure 22. Connection to setpoint output

Table of Contents