EasyManua.ls Logo

Logic DLC NET Series

Logic DLC NET Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
USE AND MAINTENANCE MANUAL DLC
NET
Series
Settings
LOGIC S.r.l. - M0145Db.docx
Mod. L0006A01 of 30/05/2016
Page 40 of 78
4.2 Fieldbus communication
4.2.1 PLC hardware setting
The shared data structure is the same for both versions of the Fieldbus. It consists
of a total of 2 input bytes from PLC and 8 output bytes to the PLC.
Then, the hardware configuration made in the PLC software will have 2 output
bytes and 8 input bytes.
In the PLC hardware configuration always put before 2 bytes of output to 8
bytes of input. Otherwise you cannot establish communication.
Figure 31 shows an example of hardware configuration for Siemens PLC in
Simatic Step 7
®
development environment.
Figure 31. Hardware setting for Siemens PLC
For the supply of the GSD library files for Profibus-DP
®
Protocol and GSDML
for Profinet
®
contact the customer service Logic.
4.2.2 Data structure
Looking at the PLC side, the data structure provides 2 output bytes and 8 bytes of
input. Especially, you can read the data weight from the instrument in 32-bit
format, a diagnostic word and stable weight threshold currently set, also
expressed as a 16bit word. The 2 output bytes are used to set within the
instrument a new value of the stable weight threshold.
The exact meaning of each data exchanged is described in Table 22.

Table of Contents