Note
While making wiring connections at the control terminals ensure that the total cable length
does not exceed 165 ft (50 m).
Ensure that the length of any safety related wiring does not exceed 100 ft (30 m).
Ensure that the cable length between the keypad and the inverter does not exceed 10 ft
(3.04 m). Cable connections longer than 10 ft (3.04 m) may cause signal errors.
Use ferrite material to protect signal cables from electro-magnetic interference.
Take care when supporting cables using cable ties, to apply the cable ties no closer than 6
inches from the inverter. This provides sufficient access to fully close the terminal cover.