cartridges, make sure that the O-ring is cleaned and lightly greased (e.g. with Vaseline).
When using a chemical lter cartridge (5 micron chem.) it must be changed regularly (twice a year or after 150 m
3
ow).
High-pressure nozzles instructions
Check the spray pattern of the high-pressure nozzles regularly. If necessary, the nozzles can be unscrewed and
disassembled for cleaning. In the case of limescale deposits, cleaning may be done in a descaling bath / acetic
acid bath/ultrasonic bath. Afterwards rinse thoroughly and blow out.
If there are leaks in the O-ring seals of the nozzles, the O-rings must be replaced. If the nozzle on the nozzle body
or on the spray head is damaged by mechanical or chemical overloading, the complete nozzle must be replaced.
If nozzles drip, the spring valve may be worn out and should be replaced.
Cleaning instructions
The system must be protected as good as possible against contamination. In particular, dirt on the pump unit and
the control unit must be removed regularly. Contamination can endanger the function of the system, for example
through inadequate ventilation.
Do not clean the pump unit, control unit and other electrical components with a high-pressure cleaner. Before
cleaning with water, cover all openings which have to be protected - for safety and/or functional reasons – against
water, steam or detergent penetration. After cleaning, the covers must be completely removed.
7. TROUBLESHOOTING
7.1 Faults Touch controller
FAULT CAUSE REMEDY
Error message
“No water alarm”
Note: the controller also
switches the alarm relay (see
wiring plans).
The error message is triggered if no
signal is present at the pressure switch
input of the controller after the Press.
wait time. This can have the following
causes:
• press. wait time too short
• duration for pressure build-up too
long
• no sufcient pressure is reached
(switching point of the pressure
switch is 25 bar) - compare with
pressure gauge!
• pressure switch does not switch
• electrical connection of the
pressure switch faulty
• Increase Press. wait time at the
controller (System parameter)
• Remove cause of slow pressure
build-up
• Remove the cause of insufcient
pressure (see further notes)
• Replace pressure switch
• Repair connections
Error message “Tank level” • Tank level is or was too low
• Electrical connection of the oat
switch faulty
• Ensure enough ow into the tank
• Repair connections/components
Malfunction of outputs or inputs • Relay or other parts of the boards
worn out/defective.
• Replace the affected board.
When replacing the mainboard,
the required software must be
installed (please specify the
version when ordering).
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
lubingsystem.com
c
lubingsystem.com
lubingsystem.com