5. This equipment has been evaluated for use in a continuous
ambient temperature of up to 50° C.
6. AC branch circuits to this equipment must be protected
with either fuses or circuit breakers sized as required by
the National Electric Code (NEC) and/or local codes. The
size of the overcurrent protector used must not exceed 30
amperes. Refer to the equipment ratings to assure rating of
equipment will not exceed 80% of the value of the
protector chosen.
7. An accessible ac disconnect/protection device to remove
ac power from the equipment in the event of an emergency
must be provided.
8. For installations in the United States, UL Listed
compression connectors should be used to terminate UL
Listed field-wired conductors where required. For all
installations, the appropriate connector should be applied
only to the correct size conductor as specified by the
connector manufacturer, using only the connector
manufacturer’s recommended tooling or tooling approved
for that connector.
9. For electrical connections requiring crimp-on lugs, make
sure the proper crimping tools and dies are used
(information for these connections are provided in the
product documentation). Torque electrical connections to
the values specified on labels or in the product
documentation.
10. This equipment is intended to be mounted in a rack with
the dimensions as noted in Section 5, Installation. For
proper ventilation, the front and back of the rectifier must
not be obstructed (refer to Section 5, Installation, for space
requirements).