2000 50A -48V 364A-3 SR Series Rectifier
Issue 6 January 1997 Operating Controls and Displays 6 - 1
6 Operating Controls and
Displays
General This section describes the components of the 364A3 rectifier the
user sees and operates manually.
Specifics The 364A3 rectifier front panel controls, switches, indicators,
displays, and connectors are shown in Figure 6-1. Each item is
identified in the figure by an index number. The function of each
item, called out by index number assigned, is listed and
described below.
Volts Adj - Eq (1) A screwdriver-adjustable recessed potentiometer, used during
equalize mode to set rectifier output voltage. The range of
control is between 48 and 58V.
V-Plant Test
Jacks (2, 3)
Jacks are used to measure the plant voltage at the remote sense
point.
V-Rect Test
Jacks (4, 5)
Jacks are used to measure the rectifier internal sense point
voltage. This voltage is measured before the dc output circuit
breaker.
Volts Adj - Fl (6) A screwdriver-adjustable recessed potentiometer adjustment,
used during float mode to set rectifier output voltage. The range
of control is between 48 and 58V.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies Lineage 2000 SR Series and is the answer not in the manual?

Lucent Technologies Lineage 2000 SR Series Specifications

General IconGeneral
BrandLucent Technologies
ModelLineage 2000 SR Series
CategoryIndustrial Equipment
LanguageEnglish