Figure 3-16 Onyxx Boolean Output Writable
Note: The default operation is normal logic (closed contacts at DO if input value “true”). If needed, you can “flip”
this logic in the ProxyExt by assigning a Conversion type of “Reverse Polarity.” This causes the “reversed” boolean
state going from input to output.
CounterInputPoint
A CounterInputPoint is a NumericPoint with OnyxxCounterInputProxyExt. The Counter Input Point is used in the station
database to count dry-contact pulses with a change-of-state (COS) frequency of up to 50 Hz and a 50% duty cycle.
These points will increment on both sides of a pulse, therefore a full cycle with be 2 counts. If a single change in value
is desired, the user will need to divide the result by 2.
Note: Minimum dwell time must be > 2ms.
Figure 3-17 Onyxx Counter Input Point
Config Properties
Counter Input points contain two properties to assist user who need to have the output value rollover at a specified
time.