Item Function Indication range
4 Output current Iem 0~200% of the rated current of the motor
5 Output torque 0~300% of the rated torque of the motor
6 Output torque current 0~300% of the torque current
7
Rotating speed of motor (V/F
control disabled)
0~Maximum rotating speed
8 Output voltage 0~150% of the rated voltage of the drive
9 AI1 voltage -10V~10V/4~20mA
10 AI2 voltage -10V~10V/4~20mA
11 Reserved
12 Output power 0~200% of the rated power
13~16 Reserved
17
HOST device expansion
function 1
0
65535
18 Reserved
19 Percentage of bus card 0
65535
This function code defines the maximum output frequency when the terminal Y1 is used as the DO
high-speed pulse output terminal.
This function code defines three different central point modes when the terminal Y1 is used as the DO
high-speed pulse output terminal.
0: No central point. As shown in Fig.6-29.
Fig.6-29 No central point mode
The values corresponding to the pulse output frequency are all positive.
1: Central point mode 1. As shown in Fig.6-30.
Pulse output central point selection
0~2
(
0
)
P09.31
Maximum output pulse frequency
0.1~50.0kHz
(
10.0 kHz
)
P09.30