147
Fig.6-30 Central point mode 1
The pulse output has a central point. The frequency at the central point is half of the maximum pulse
output frequency P09.30. When the output pulse frequency is lower than the central point frequency, the
corresponding values are positive.
2: Central point mode 2
The pulse output has a central point. The frequency at the central point is half of the maximum pulse
output frequency P09.30. When the output pulse frequency is higher than the central point frequency, the
corresponding values are positive.
Percentage
Pulse
frequency
0
P09.30
P09.30
2
100%
-100%
Fig.6-31 Central point mode 2
This function code defines the filtering time of the output pulse. The longer the filtering time is, the slower
the output pulse frequency change rate will be.
It is used together with the No. 20 function of the digital output terminal.
This function code is relative to the maximum output frequency P02.15. It is used together with No. 10
function of the digital output terminal.
Zero-speed threshol
d
0.0~100.0%
(
1.0%
)
P09.34
Flux detection value
10.0~100.0%
(
100.0%
)
P09.33
Pulse output filtering time
0.00~10.00s
(
0.05s
)
P09.32