154
Item Function Indication range
motor
6
Output torque
0 ~ 300% of the rated torque of the
motor
7
Output torque current
0 ~ 300% of the rated torque of the
motor
8
Output voltage
0 ~ 120% of the rated voltage of the
drive
9
Bus voltage
0~800V
10
AI1
0~Maximum analog input
11 AI2 0~Maximum analog input
12 Reserved
13 Output power
0 ~ 200% of the rated power of the
motor
14 Percentage of host device 0
~
4095
15~23 Reserved
24 Motor rotating speed (bipolar)
Negative maximum output frequency ~
maximum output frequency
25 Reserved
26 Percentage of bus card 0~4095
Note
1. When the function corresponding to the AO output is unipolar, the indication value corresponding to the
minimum output has the minimum absolute value, while the indication value corresponding to the maximum
output has the maximum absolute value. When the function is bipolar, the indication value corresponding to
the minimum output is the smallest, while the indication value corresponding to the maximum output is the
biggest.
2. When the AO output is current, it is suggested that the external equivalent resistance not exceed 400ohm.
For the AO1 analog output, if you need to change the display range or correct the meter error, you can
adjust the output gains to achieve the goal.
The analog output zero offset takes 100% as the maximum output (10V or 20mA), and adopts the
percentage as the unit to set the up and down translation. Taking the output voltage as an example, the
adjustment relations before and after the adjustment are as shown as below:
AO1 output value = output gain x value before adjustment + zero offset correction x 10V
The curves for the relation between analog output and gains, between analog output and zero offset
correction are as shown in Fig.6-41 and Fig.6-42.