23
Terminal type 6
Applicable models: MV200G-4T90 ~ MV200G-4T315, MV200P-4T110 ~ MV200P-4T315
Terminal Function
R/L1, S/L2, T/L3 Three-phase AC 380V input terminals
P, + D C Reserved for external DC reactor, connected with copper bus
upon delivery
P, - D C Reserved for external braking resistor
-DC DC negative bus output terminals
U/T1, V/T2, W/T3 Three-phase AC output terminals
Terminal type 7
Applicable models: MV200G-4T355 ~ MV200G-4T400, MV200P-4T355 ~ MV200P-4T400
Terminal Function
R/L1, S/L2, T/L3 Three-phase AC 380V input terminals
P, + D C Reserved for external DC reactor, connected with copper bus
upon delivery
P, N Reserved for external braking resistor
-DC DC negative bus output terminals
U/T1, V/T2, W/T3 Three-phase AC output terminals
Note
In the common DC bus application, the positive pole and the negative pole of the DC input should be
connected to the terminals +DC and -DC respectively, and then the limiting current resistor used for protecting
the rectifier inside drive will be valid when powering on.