67
(kWh)
P01.15
Low level of
output
(kWh)
Output
(kWh)
0~9999kWh 1kWh 0 × √ *
P01.16 Bus voltage Bus voltage 0~800V 1V 0 × √ *
P01.17
Operation
state of the
drive
Operation
state of the
drive
0~FFFFH
Bit 0: RUN/STOP
Bit 1: REV/FWD
Bit 2: Running at zero speed
Bit 3: Accelerating
Bit 4: Decelerating
Bit 5: Running at constant speed
Bit 6: Pre-exciting
Bit 7: Tuning
Bit 8: Over-current limiting
Bit 9: DC over-voltage limiting
bit10~bit11:Reserved
Bit 12: Drive in fault
bit13~bit15:Reserved
1 0000 × √ *
P01.18
State of
digital input
terminal
DI terminal
state
0~3FH, 0: off; 1: on
The high-speed pulse reference will
not be refreshed synchronously
1 00 × √ *
P01.19
State of
digital
output
terminal
DO terminal
state
0~7H, 0: open; 1: close
The high-speed pulse output will not
be refreshed synchronously
1 0 × √ *
P01.20
AI1 input
voltage
AI1 input
voltage
-10.00~10.00V 0.01V 0.00 × √ *
P01.21
AI2 input
voltage
AI2 input
voltage
-10.00~10.00V 0.01V 0.00 × √ *
P01.22 Reserved
P01.23 AO1 output AO1 output
0.0~100.0%
(percentage relative to the full range)
0.1% 0.0%
× √ *
P01.24 Reserved
P01.25
Process
closed loop
reference
Process
closed loop
reference
-100.0~100.0%
(percentage relative to the full range)
0.1% 0.0%
× √ *
P01.26
Process
closed loop
feedback
Process
closed loop
feedback
-100.0~100.0%
(percentage relative to the full range)
0.1% 0.0%
× √ *
P01.27
Process
closed loop
error
Process
closed loop
error
-100.0~100.0%
(percentage relative to the full range)
0.1% 0.0%
× √ *
P01.28
Process
closed loop
output
Process
closed loop
output
-100.0~100.0%
(percentage relative to the full range)
0.1% 0.0%
× √ *