EasyManua.ls Logo

Megmeet MV200 Series - Page 74

Default Icon
235 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74
braking
2:Start after speed tracking (including
the judgment of direction)
P08.01
Startup
delay time
Startup delay
time
0.00~30.00s 0.01s 0.00s ×
P08.02
Startup
(dwell)
frequency
Startup
frequency
0.00~60.00Hz 0.01Hz 0.00Hz ×
P08.03
Startup
frequency
retention
time
Startup
frequency
retention
time
0.00~10.00s 0.01s 0.00s ×
P08.04
Startup DC
braking
current
Startup DC
braking
current
G: 0.0% ~ 100.0% of the rated current
of the drive
P: 0.0% ~ 50.0% of the rated current of
the drive
0.1%
0.0
×
P08.05
Startup DC
braking
time
Startup DC
braking time
0.00 (Disabled)
0.01~30.00s
0.01s 0.00s ×
P08.06 Stop mode Stop mode
0: Decelerate to stop
1: Coast to stop
2:Decelerate to stop + DC braking
1 0 × ×
P08.07
Stop
frequency
detection
Stop
frequency
detection
0.00~150.00Hz 0.01Hz 0.50Hz × ×
P08.08
Stop
frequency
detection
retention
time
Stop
frequency
detection
retention
time
0.00~10.00s 0.01s 0.00s ×
P08.09~
P08.11
Reserved
P08.12
Initial
frequency
for stop DC
braking
Initial
frequency for
stop braking
0.00~60.00Hz 0.01Hz 0.00Hz ×
P08.13
Waiting
time for
stop DC
braking
Waiting time
for stop
braking
0.00~10.00s 0.01s 0.00s ×
P08.14
Stop DC
braking
current
Stop DC
braking
current
G: 0.0% ~ 100.0% of the rated current
of the drive
P: 0.0% ~ 50.0% of the rated current of
the drive
0.1% 0.0% ×
P08.15
Stop DC
braking
time
Stop DC
braking time
0.0 (Disabled)
0.01~30.00s
0.01s 0.00s ×
P08.16
Selecting
restart
Restart upon
power fault
0: Disabled
1: Enabled
1 0 × ×

Table of Contents