81
function
selection
selection
selection
0: No function
1: Main reference frequency setting
2: Auxiliary reference frequency setting
3~8: Reserved
9: Main reference frequency setting
(unipolar)
A: Auxiliary reference frequency
setting (unipolar)
B: Motor temperature detection
C: Output voltage offset (under V/F)
D: Output voltage (under V/F)
E: Reserved (command rate
numerator)
Tens place of LED: AI2 function
selection is the same as above
P10.02 AI1 filtering AI1 filtering 0.000~10.000s 0.001s 0.010s × √ ○
P10.03 AI2 filtering AI2 filtering 0.000~10.000s 0.001s 0.010s × √ ○
P10.04 Reserved
P10.05
Analog
curve
selection
Analog curve
selection
Unit place of LED: AI1 curve selection
0: Line 1
1: Line 2
2: Curve 1
Tens place of LED: AI2 curve selection
The same as above
Hundreds place of LED: Reserved
Thousands place of LED: Pulse input
curve selection
The same as above
1 0010H √ √ ○
P10.06
Maximum
reference of
line 1
Maximum
reference 1
P10.08~100.0% 0.1% 100.0% √ √ ○
P10.07
Actual
value
correspond
s to the
maximum
reference of
line 1
Actual value
corresponds
to maximum
reference 1
Frequency reference: 0.0~100.0% of
Fmax
Magnetic flux: 0.0~100.0%Φe
0.1% 100.0% √ √ ○
P10.08
Minimum
reference of
line 1
Minimum
reference 1
0.0%~P10.06
0.1% 0.0% √ √ ○
P10.09
Actual
value
correspond
s to the
minimum
reference of
Actual value
corresponds
to minimum
reference 1
The same as P10.07
0.1% 0.0% √ √ ○