4: Output current I
em
(0~2 * I
em
)
5: Output torque (0~3 * T
em
)
6: Output torque current (0~3*I
tem
)
7: Motor rotating speed (0~Maximum
output frequency)
8: Output voltage (0~1.5 * V
e
)
9: AI1-10~10V/4~20mA
10: AI2-10~10V/4~20mA
11: Reserved
12: Output power (0~2*P
e
)
13~16: Reserved
17: Percentage of host device
(0~65535)
18: Reserved
19: Percentage of bus card
Only the following function No. will be
shown in shortcut menu: 0~8
P09.30
Maximum
output
pulse
frequency
Maximum
output pulse
0.1~50.0 (Maximum 50.0k) 0.1kHz 10.0
P09.31
Pulse
output
central
point
selection
Pulse output
central point
0: Without central point
1: With central point
It is (P09.30)/2. It is positive when the
frequency is less than the central point
frequency
2: With central point
It is (P09.30)/2. It is positive when the
frequency is larger than the central
point frequency
1 0 ×
P09.32
Pulse
output
filtering time
Pulse output
filtering time
0.00~10.00s 0.01s 0.05 ×
P09.33
Flux
detection
value
Flux
detection
value
10.0~100.0%
0.1% 100.0% ×
P09.34
Zero-speed
threshold
Zero-speed
threshold
0.0~100.0% of maximum frequency 1.0%
1.0
×
Group P10: Analog input/output terminal parameters
P10.00
Analog
input
properties
Analog input
properties
Unit place: AI1
0: Voltage input
1: Current input
Tens place: AI2
0: Voltage input
1: Current input
1 00 ×
P10.01
Analog AI AI function
Unit place of LED: AI1 function
1 000 ×