88
P13.02
Multi-stage
reference 2
Multi-stage
reference 2
0.0%~100.0% corresponds to
“minimum frequency ~ maximum
frequency”
When it is multi-stage closed loop
reference:
-100.0%~100.0% corresponds to
“-10V~+10V”
0.1% 20.0% × √ ○
P13.03
Multi-stage
reference 3
Multi-stage
reference 3
0.1% 40.0% × √ ○
P13.04
Multi-stage
reference 4
Multi-stage
reference 4
0.1% 60.0% × √ ○
P13.05
Multi-stage
reference 5
Multi-stage
reference 5
0.1% 80.0% × √ ○
P13.06
Multi-stage
reference 6
Multi-stage
reference 6
0.1% 90.0% × √ ○
P13.07
Multi-stage
reference 7
Multi-stage
reference 7
0.1% 100.0% × √ ○
P13.08
Multi-stage
reference 8
Multi-stage
reference 8
0.1% 10.0% × √ ○
P13.09
Multi-stage
reference 9
Multi-stage
reference 9
0.1% 20.0% × √ ○
P13.10
Multi-stage
reference
10
Multi-stage
reference 10
0.1% 40.0% × √ ○
P13.11
Multi-stage
reference
11
Multi-stage
reference 11
0.1% 60.0% × √ ○
P13.12
Multi-stage
reference
12
Multi-stage
reference 12
0.1% 80.0% × √ ○
P13.13
Multi-stage
reference
13
Multi-stage
reference 13
0.1% 90.0% × √ ○
P13.14
Multi-stage
reference
14
Multi-stage
reference 14
0.1% 100.0% × √ ○
P13.15
Multi-stage
reference
15
Multi-stage
reference 15
0.1% 100.0% × √ ○
P13.16
Simple PLC
running
mode
selection
PLC running
mode
Unit place of LED: PLC running mode
0: Stop after single cycle
1: Hold the end value after single cycle
2: Continuous cycle
Tens place of LED: Start mode
0: Restart from the first section
1: Continue to run from the stage of the
stop (or fault) moment
2: Continue to run from the stage and
frequency of the stop (or fault) moment
Hundreds place of LED: power down
storage
0: No storage
1: Save the stage and frequency at the
1 0000 × √ ×