99
motor (Er.oL1)
1: Relative to rated current of the drive
(Er.oL2)
P97.04
Overload
pre-alarm
detection
level
Overload
detection
level
20.0%~200.0% 0.1% 130.0% × √ ○
P97.05
Overload
pre-alarm
detection
time
Overload
detection
time
0.0~60.0s 0.1s 5.0s × √ ○
P97.06
Motor
over-temper
ature
protection
point
Motor
over-temper
ature
protection
point
0.00~10.00V 0.01 10.00 × √ ○
P97.07
Over-voltag
e stall
selection
Over-voltage
stall
selection
0: Disabled (when the braking resistor
is installed)
1: Enabled
1 1 × √ ×
P97.08
Over-voltag
e point at
stall
Over-voltage
point at stall
120.0%~150.0%Udce
0.1%
140.0%
× √ ×
P97.09
Auto
current
limiting
action
selection
Auto current
limiting
action
0: Disabled at constant speed
1: Enabled at constant speed
Note: Always enabled for
acceleration/deceleration
1 1 × √ ×
P97.10
Auto
current
limiting
level
Current
limiting level
20.0%~200.0%Ie 0.1%
G:150.0
%;
P:110.0
%
× √ ×
P97.11
Frequency
reduction
rate upon
current
limiting
Frequency
reduction
rate
0.00~99.99Hz/s 0.01Hz/s
10.00
Hz/s
× √ ○
P97.12
Grounding
short circuit
detection
upon
power-up
Grounding
short circuit
detection
upon
power-up
0: Disable
1: Enable (enabled for model of 7.5kW
and below)
1 1 × √ ○
P97.13
Auto reset
times
Auto reset
times
0: No function
1~100: Auto reset times
Note: Auto reset is not available for
module protection, external device
fault and AI over-current fault
1 0 × √ ×
P97.14
Auto reset
interval
Reset
interval
2.0~20.0s per time 0.1s 5.0s × √ ×
P97.15
The first First new
0: No abnormal record
1 0 × √ *