98
to stop
1 : Activate protection and coast to
stop
2 : Alarm and keep running
P97.02
Fault
protection
and alarm
property
setting 3
Fault
protection
and alarm
property
setting 3
Unit place of LED: Action upon
temperature sampling disconnection
0 : Activate temperature protection
upon inverter and rectifier module and
stop in the stop mode
1 : Activate temperature protection
upon inverter and rectifier module and
coast to stop
2 : Temperature alarm upon inverter
and rectifier module and keep running
3 : No action to rectifier, activate
temperature protection upon inverter
and stop in the stop mode
Tens place of LED: Action upon
under-voltage fault indication
0 : No action
1 : Action (under-voltage is regarded
as a kind of fault)
Hundreds place of LED: Action upon
auto-reset interval fault indication
0 : No action
1 : Action
Thousands place of LED: Fault lockup
function selection
0 : Prohibited
1 : Open (without fault output)
2 : Open (with fault output)
1 0000 × ×
P97.03
Overload
protection
setting for
motor
Overload
protection
setting
Unit place of LED: Overload
compensation mode
0: No action
1: Common motor (with low-speed
compensation)
2: Variable-frequency motor (without
low-speed compensation)
Tens place of LED: Overload pre-alarm
detection selection
0: Always detect
1: Detect only at constant speed
Hundreds place of LED: Overload
pre-alarm action selection
0: Alarm and keep running
1: Activate protection and coast to stop
Thousands place of LED: Overload
detection level selection
0: Relative to rated current of the
1 0001 × ×