Group P97: Protection and fault parameters
P97.00
Fault
protection
and alarm
property
setting 1
Fault
protection
and alarm
property
setting 1
Unit place of LED: Action upon
communication fault
0: Activate protection and coast to stop
1: Alarm and keep running
2: Alarm and stop in the stop mode
(only in serial port control mode)
3: Alarm and stop in the stop mode (in
all control modes)
Tens place of LED: Action upon
contactor abnormality
0: Activate protection and coast to stop
1: Alarm and keep running
Hundreds place of LED: Action upon
EEPROM abnormality
0: Activate protection and coast to stop
1: Alarm and keep running
Thousands place of LED: Action upon
24V/±10V short circuit
0: Activate protection and coast to stop
1: Alarm and keep running
1 0000 × ×
P97.01
Fault
protection
and alarm
property
setting 2
Fault
protection
and alarm
property
setting 2
Unit place of LED: Action upon phase
loss
0: Activate protection upon input and
output phase loss
1: No protection upon input phase loss
2: No protection upon output phase
loss
3: No protection upon input and output
phase loss
Tens place of LED: Action upon loss of
external analog frequency input
0: No action
1: Activate protection and coast to stop
2: Alarm and keep running
Hundreds place of LED: Action upon
motor overheat
0: Activate protection and decelerate to
stop
1: Activate protection and coast to stop
2: Alarm and keep running
Thousands place of LED: Action upon
analog input (AI1, AI2) fault
0 : Activate protection and decelerate
1 0000 × ×