96
d power-on
hours
power-on
hours
P16.10
Accumulate
d running
hours
Accumulated
work hours
0 ~ maximum 65535 hours 1hour 0 × *
P16.11
Accumulate
d running
hours of fan
Accumulated
running
hours of fan
0 ~ maximum 65535 hours 1hour 0 × *
Group P40: Fieldbus option parameters
P40.00 Option type Option type
000: No communication option
001: Profibus-DP
Others: Reserved
1 0 × *
P40.01
Option
hardware
version
Option
hardware
version
0.00~99.99 1 0 × *
P40.02
Option
software
version
Option
software
version
0.00~99.99 1 0 × *
P40.03
P40.21
Reserved Reserved
P40.22
Option
reset
selection
Option reset
selection
0: Do not reset or reset successfully
1: Enable option reset
1 0 ×
P40.23
Profibus-DP
PPO type
selection
Profibus-DP
PPO type
selection
1~5:PPO1~PPO5 1 1 ×
P40.24
Communica
tion baud
rate display
or selection
Communicat
ion baud rate
display or
selection
Profibus-DP: Display the current
communication baud rate
0: 9.6 kbps; 1: 19.2 kbps;
2: 45.45 kbps; 3: 93.75 kbps;
4: 187.5 kbps; 5: 500 kbps;
6: 1.5 Mbps; 7: 3 Mbps;
8: 6 Mbps; 9: 12 Mbps
Other options: Reserved
1 0 ×
P40.25
Option fault
display
Option fault
display
0: Option is normal
1:Option wire-break or other faults
1 0 × *
P40.26
Communica
tions
disconnecti
on
detection
time
Communicat
ions
disconnectio
n detection
time
0.0~10.0s 0.1 0.0 ×
P40.27
P40.29
P40.30
P40.39
Bus output
data
mapping
Bus output
data
mapping
0~9999
Please refer to the Option Manual for
details
1 0 ×