95
BIT3: DC bus voltage
P16.02
LED display
parameter
selection
when stop
Stop display
Binary setting:
0: No display; 1: Display
Unit place of LED:
BIT0: Preset frequency (Hz)
BIT1: Running speed (r/min)
BIT2: Preset speed (r/min)
BIT3: DC bus voltage (V)
Tens place of LED:
BIT0: Running line speed (m/s)
BIT1: Preset line speed (m/s)
BIT2: Analog closed loop feedback (%)
BIT3: Analog closed reference (%)
Hundreds place of LED:
BIT0: AI1 (V)
BIT1: AI2 (V)
BIT2: Reserved
BIT3: Terminal status (without unit)
Note: The default display shall be set
frequency when all the parameters are
0
1 009H ×
P16.03
Line speed
coefficient
Line speed
coefficient
0.1~999.9%
Line speed = Operation frequency ×
P16.03
Preset line speed = Preset frequency
× P16.03
0.1% 1.0% ×
P16.04
Rotating
speed
display
coefficient
Rotating
speed
coefficient
0.1~999.9%
Running rotating speed = running
frequency × motor rated rotating
speed/motor rated frequency × P16.04
Preset rotating speed = Preset
frequency × motor rated rotating
speed/motor rated frequency × P16.04
0.1% 100.0% ×
P16.05
Close loop
analog
display
coefficient
Closed loop
display
coefficient
0.1~999.9%
Note: The close loop analog
reference/feedback displays range is
0~9999.9
0.1% 100.0% ×
P16.06
Inverter
module
temperature
Inverter
module
temperature
0.0~150.0 0.1 0.0 × *
P16.07
Rectifier
module
temperature
Rectifier
module
temperature
0.0~150.0 0.1 0.0 × *
P16.08
Motor
temperature
measured
Motor
temperature
measured
0~200℃℃ 1 0 × *
P16.09
Accumulate Accumulated
0 ~ maximum 65535 hours 1hour 0 × *