94
1: MODEM (232)
P15.02
Local
address
Local
address
0~247, 0 is the broadcast address 1 5 × ×
P15.03
Communica
tion timeout
detection
time
Communicat
ion timeout
time
0.0~1000.0s 0.1 0.0s × ×
P15.04
Response
delay of the
drive
Response
delay of the
drive
0~1000ms 1 5ms × ×
P15.05
Reserved
function 1
for user
Reserved
function 1 for
user
0~65535 1 0 ×
P15.06
Reserved
function 2
for user
Reserved
function 2 for
user
0~65535 1 0 ×
Group P16: Keyboard display setting parameters
P16.00
LED display
parameter
selection 1
when
running
Running
display 1
Binary setting:
0: No display; 1: Display
Unit place of LED:
BIT0: Output frequency (Hz)
BIT1: Preset frequency (Hz flashing)
BIT2: Output current (A)
Tens place of LED:
BIT0: Running rotating speed (r/min)
BIT1: Preset rotating speed (r/min,
flashing)
BIT2: Running line speedm/s
BIT3: Preset line speed (m/s, flashing)
Hundreds place of LED:
BIT0: Output power
BIT1: Output toque (%)
Note: The default display shall be
output frequency when all the
parameters are 0
1 007H ×
P16.01
LED display
parameter
selection 2
when
running
Running
display 2
Binary setting:
0: No display; 1: Display
Unit place of LED:
BIT0: Output voltage (V)
BIT1: AI1V
BIT2: AI2V
Tens place of LED:
BIT0: Analog closed loop feedback (%)
BIT1: Analog closed loop reference
(%, flashing)
BIT2: Terminal status (without unit)
1 00 ×