93
(feedback lost) or “Er.Fbo” (feedback
exceeding limit)
Tens place: PID limit setting error
processing selection
0: Continue to run, no alarm
1: Continue to run and display “AL.PIL”
2: Coast to stop and display “Er.PIL
P14.26
PID
feedback
lost
detection
value
PID
feedback
lost
detection
value
0.0~100.0% 0.1% 0.0% ×
P14.27
PID
feedback
lost
detection
time
PID
feedback
lost
detection
time
0.0s~25.0s 0.1s 1.0s ×
P14.28
PID
feedback
exceeding
limit
detection
value
PID
feedback
exceeding
limit
detection
value
0.0~100.0% 0.1% 100.0% ×
P14.29
PID
feedback
exceeding
limit
detection
time
PID
feedback
exceeding
limit
detection
time
0.0s~25.0s 0.1s 1.0s ×
Group P15: Communication parameters
P15.00
Protocol
selection
Protocol
selection
0: MODBUS
1: Reserved
1 0 × ×
P15.01
Communica
tion
configuratio
n
Communicat
ion
configuration
Unit place of LED: Baud rate selection
0: 4800BPS
1: 9600BPS
2: 19200BPS
3: 38400BPS
4: 115200BPS
5: 125000BPS
Tens place of LED: Data format
0: 1-8-2-N format, RTU
1: 1-8-1-E format, RTU
2: 1-8-1-O format, RTU
3: 1-7-2-N format, ASCII
4: 1-7-1-E format, ASCII
5: 1-7-1-O format, ASCII
Hundreds place of LED: wiring mode
0: Direct cabling (232/485)
1 001 × ×