92
value
P14.11
Differential
amplitude
limit
Differential
amplitude
limit
0.0~100.0% 0.1% 10.0% ×
P14.12
Sampling
cycle
Sampling
cycle
0.001~50.000s 0.001s 0.010s ×
P14.13
Deviation
limit
Deviation
limit
0.0~20.0%
(Corresponds to PID reference)
0.1% 2.0% ×
P14.14
PID upper
limit
channel
PID upper
limit channel
0: P14.16 digital reference;
1:AI1
2:AI2
1 0 ×
P14.15
PID lower
limit
channel
PID lower
limit channel
0: P14.17 digital reference;
1:AI1
2:AI2
1 0 ×
P14.16
PID upper
limit digital
setting
PID upper
limit
digital setting
P14.17~100.0% 0.1% 100.0% ×
P14.17
PID lower
limit
digital
setting
PID lower
limit digital
setting
0.0%~ P14.16 0.1% 0.0% ×
P14.18
Output
filtering time
Output
filtering time
0.000~10.000s 0.001s 0.010s ×
P14.19
PID output
feature
selection
PID output
feature
selection
0: PID output is positive
1: PID output is negative
1 0 × ×
P14.20
PID offset
value
PID offset
value
-100.0~100.0% 0.1%
0.0
×
P14.21
PID output
gain
PID output
gain
0.0~250.0 0.1 1.0 ×
P14.22
REV
selection of
PID output
REV
selection of
PID output
0: When the PID output is a negative
value, there is no limit
1: When the PID output is a negative
value, the output is negative
1 1 × ×
P14.23
PID pre-set
frequency
PID pre-set
frequency
0.00~3000.00Hz 0.01Hz 0.00Hz ×
P14.24
PID pre-set
frequency
retention
time
PID pre-set
frequency
retention
time
0.0~3600.0s 0.1s 0.0s × ×
P14.25
PID fault
detection
selection
PID fault
detection
selection
Unit place: PID feedbacks the fault
detection selection
0: Continue to run, no alarm
1: Continue to run and display
“AL.FbL” (feedback lost) or “AL.Fbo
(feedback exceeding limit)
2: Coast to stop and display “Er.FbL
1 00 × ×