Technical Bulletin—TC-9100 Universal Controller 51
Digital Inputs Analog Inputs
System 91 N2
Communications
Bus
Power
Supply
Power Common
RT+
10 11 12 13 14 15 22 24 25 26 50 51 52 53 54 55
RT COM SH.
24 VAC
Live
~
24 VAC
Common
Ground
Analog Common
Digital Common (blue)
Supply (red)
Signal (white)
10 11 12 13
DI2
Analog Inputs, 0 - 10 VDC
AI1 AI2 15V AI3
ACOM
15V AI4
ACOM
15V
Voltage-Free
Contacts
Mode
LED
DI1 DI2
Digital (Triac) Outputs
Isolated Switched Outputs
(rated at max. 24 VAC, 0.5 amp)
DO3
DO4DO5DO6DO7
41 4043 4245 4447 4649 48
Analog Outputs
Analog Outputs
0 - 10 VDC
Power Common
31 3033 3235 34
AO1a
+
AO1b
+
AO2
+
Power Common
123
RS-485
Cable
HX-9100-8001
Condensation
Senso
r
(See also "Wiring to TM-9180 Room
Command Module" diagram.)
Figure 18: TC-9100-x000 (with Analog Outputs)
Controller Wiring
Notes: 1. The Digital (triac) Outputs are isolated from all other internal circuits.
2.
The Analog Outputs and Digital Inputs have the same “common” as the 24 VAC
Power Supply.
3.
The Analog Input “common” is the same as the internal logic circuit common, but is
isolated from the 24 VAC Power Common.
4.
The System 91 N2 Communications Bus is isolated from all other internal circuits.