52 Technical Bulletin—TC-9100 Universal Controller
Digital Inputs Analog Inputs
System 91 N2
Communications
Bus
Power
Supply
Power Common
RT+
10 11 12 13 14 15 22 24 25 26 50 51 52 53 54 55
RT– COM SH.
24 VAC
Live
~
24 VAC
Common
Ground
Analog Common
Digital Common (blue)
Supply (red)
Signal (white)
10 11 12 13
DI2
Analog Inputs, 0 - 10 VDC
AI1 AI2 15V AI3
ACOM
15V AI4
ACOM
15V
Voltage-Free
Contacts
Mode
LED
DI1 DI2
Digital (Triac) Outputs
Isolated Switched Outputs
(rated at maximum 24 VAC, 0.5 amp)
DO4DO5DO6DO7 DO3
41 4043 4245 4447 4649 48
DO2
39 38
DO1
37 36
Power Common
3 2 1
utc0wr3
HX-9100-8001
Condensation
Sensor
RS-485
Cable
(See also "Wiring to TM-9180 Room
Command Module" diagram.)
Figure 19: TC-9100-x001 (without Analog Outputs)
Controller Wiring
Notes: 1. The Digital (triac) Outputs are isolated from all other internal
circuits.
2. The Digital Inputs have the same “common” as the 24 VAC
Power Supply.
3. The Analog Input “common” is the same as the internal logic
circuit common, but is isolated from the 24 VAC Power
Common.
4. The System 91 N2 Communications Bus is isolated from all
other internal circuits.

Table of Contents