Technical Bulletin—TC-9100 Universal Controller 73
Item Type MEM R/W Tag Description
Hex Dec
85 133 2 Bytes D WP TCS2 Controller Options 2
X2 X1 ADC Selection
=00 Select AI1
=01 Select AI2
=10 Select AI3
=11 Select AI4
X3=1 AI1 not overridden by TM-9180
X4=0 Alternate Mode Timing = 2 Hours
X4=1 Alternate Mode Timing = 1 Hour
X5=0 not used (Must be set to 0)
X6=0 0=50 Hz Power Line
X6=1 1=60 Hz Power Line
X7=0 not used (Must be set to 0)
X8=1 Digital Output 7 is On if Mode is
COMFORT
X11...X9 Digital Input 1 Logic Mode
=000 input not used
=001 Window Open
=010 Occupancy Sensor
=011 Air Quality Sensor/Override
=100 Reverse Action
=101 General Alarm
X12=0 Open contact on Input 1 sets mode
X12=1 Closed contact on Input 1 sets mode
X15...X13 Digital Input 2 Logic Mode
=000 input not used
=001 Window Open
=010 Occupancy Sensor
=011 Air Quality Sensor/Override
=100 Reverse Action
=101 General Alarm
X16=0 Open contact on Input 2 sets mode
X16=1 Closed contact on Input 2 sets mode
86 134 not used
87 135 1 Byte D W TCS1 Controller Options 1
X7...X1 not used
X8=1 REVC Reverse Action Command
88 136 not used