76 Technical Bulletin—TC-9100 Universal Controller
Item Type MEM R/W Tag Description
Hex Dec
A8 168 2 Bytes VR R CLACT Control Loop Activity
X1=1 PM1 Heating
X2=1 PM2 Heating
X3=1 PM3 Heating
X4=1 PM4 Heating
X5=1 PM5 Heating
X6=1 PM6 Heating
X7 not used
X8 not used
X9=1 PM1 Active
X10=1 PM2 Active
X11=1 PM3 Active
X12=1 PM4 Active
X13=1 PM5 Active
X14=1 PM6 Active
X15 not used
X16 not used
A9 169 2 Bytes D WP ALG2 Configuration Index 2
AA 170 Number D WP WAL Winter Authority Limit
AB 171 Number D WP SAL Summer Authority Limit