PROCEDURE TO SET DISPLAY SCALING
• Flow in Setting Display Scaling
3-step settings are necessary to set display scaling.
• Operating Procedure to Set Display Scaling
Following pages describe operating procedures in each step to set the display scaling to 0.0 – 100.0% with the input code
‘SA, 4 – 20 mA DC input as an example.
IMPORTANT
• To distinguish from the display scaling value B, the rst decimal point blinks in setting the display scaling value A.
• Both normal scaling (display scaling value A < display scaling value B) and inverted scaling (display scaling value A >
display scaling value B) can be set within the range of -1999 to 9999.
Normal Scaling
The display value increases when the input signal increases.
Inverted Scaling
The display value decreases when the input signal increases.
Display
B
A
Display Scaling
0% 100%
Input
Input
A
B
Display Scaling
Display
0% 100%
STEP 1 STEP 2 STEP 3
Setting display
scaling value A
Setting display
scaling value B
Setting decimal
point position