Process meter Input code: S4 Measurement range (conformance range) 0 – 10 V DC
Input range -1 – +11 V
Input resistance ≥ 1 MΩ
Input code: S5 Measurement range (conformance range) 0 – 5 V DC
Input range -0.5 – +5.5 V
Input resistance ≥ 1 MΩ
Input code: S6 Measurement range (conformance range) 1 – 5 V DC
Input range 0.6 – 5.4 V
Input resistance ≥ 1 MΩ
Input code: S0
(specify voltage)
Conformance range DC voltage: 0 – 19.99 V DC
Minimum span: 0.1 V
Operational range -10 – +110% of input span
Input resistance ≥ 1 MΩ
Input code: SA Measurement range (conformance range) 4 – 20 mA DC
Input range 2.4 – 21.6 mA
Input resistance 20 Ω
Input code: SB Measurement range (conformance range) 0 – 20 mA DC
Input range -2 – +22 mA
Input resistance 20 Ω
Input code: SC Measurement range (conformance range) 0 – 10 mA DC
Input range -1 – +11 mA
Input resistance 40.2 Ω
Input code: SG Measurement range (conformance range) 0 – 1 mA DC
Input range -0.1 – +1.1 mA
Input resistance 402 Ω
Input code: SJ Measurement range (conformance range) 0 – 5 mA DC
Input range -0.5 – +5.5 mA
Input resistance 80.6 Ω
Input code: SZ
(specify current)
Conformance range DC current: 0 – 50 mA DC
Minimum span: 1 mA
Operational range -10 – +110% of input span
Input resistance
5 – 250 Ω
*3
Hold input Dry contact input
Detecting level ≤ 0.8 V
Sensing Approx. 2.1 V DC, 0.03 mA
*3 Calculated as follows; Input resistance [Ω] = 250 ÷ Input current at 100% [mA]
■ INSTALLATION
Power consumption DC power 24 V DC Operational voltage range 24 V ±10%
Ripple 10% p-p max.
Approx. 0.15 W
Operating temperature -10 to +55°C (14 to 131°F)
Operating humidity 30 to 90% RH (non-condensing)
Mounting Panel ush mounting