V6 VRF 50/60Hz
9
Part 1 - General Information
4 Combination Ratio
Table 1-4.1: Indoor and outdoor unit combination ratio limitations
Type
Minimum
combination ratio
Maximum combination ratio
Standard indoor
units only
Fresh air processing
units only
Fresh air processing units and
standard indoor units together
Notes:
1. When fresh air processing units are installed together with standard indoor units, the total capacity of the fresh air processing units must not exceed 30%
of the total capacity of the outdoor units and the total combination ratio must not exceed 100%.
Table 1-4.2: Combinations of indoor and outdoor units
Sum of capacity indexes of
connected indoor units (standard
Sum of capacity indexes of connected indoor
units (fresh air processing units and standard
connected indoor
kW HP
64
Combination ratio =
Sum of capacity indexes of the indoor units
Capacity index of the outdoor units