2.19 P1: Discharge pipe high pressure protection
Digital display output
Description
Discharge pipe high pressure protection. If the system has a 3-phase protector and the 3-phase protector is connected
with the high pressure switch, the system will display P1 protection when initially powered on, and P1 protection will
disappear once the system reaches a steady state.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Discharge pressure 4.4MPa.
Recover condition: Discharge pressure 3.2MPa.
Reset method: Resume automatically.
Possible causes
Outdoor unit stop valves are closed.
High pressure/Discharge temperature switch not connected properly or has malfunctioned.
Excess refrigerant.
System contains air or nitrogen.
High pressure side blockage.
Poor condenser heat exchange.
Main PCB damaged.
Procedure
P1
ODU stop valves are closed
Yes
Open the stop valves
No
High pressure/Discharge temperature
switch connection on main PCB is loose
1
Yes
Ensure the sensor is connected properly
No
High pressure/Discharge temperature
switch has failed
2
Yes
Replace the sensor
No
Flowchart continued on next page