2.13 xH0: Communication error
Digital display output
In the error code, 'x' is a placeholder for the compressor system (compressor and related electrical components), with 1
representing compressor system A and 2 representing compressor system B.
Description
1H0 indicates a communication error between the main control chip and the compressor A inverter driver chip.
2H0 indicates a communication error between the main control chip and the compressor B inverter driver chip.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Main control chip and inverter driver chip cannot communication for 2 minutes.
Recover condition: Communication go back to normal.
Reset method: Resume automatically.
Possible causes
Incorrect compressor inverter module address setting.
Loosened communication wiring from the main PCB to
the inverter module.
Bridge rectifier damaged.
Main PCB damaged.
Compressor inverter module damaged.