V6 VRF 50/60Hz
79
Part 6 - Diagnosis and Troubleshooting
Procedure
E4
Temperature sensor connection on main
PCB is loose
1
Yes
Ensure the sensor is connected properly
No
Temperature sensor has short-circuited
or failed
2
Yes
Replace the sensor
No
Replace outdoor main PCB
Notes:
1. Outdoor ambient temperature sensor (T4) and heat exchanger temperature sensor (T3) connection is port CN1 on the main PCB (labeled 11 in Figure 5-2.1
in Part 5, 2.1Ports).
2. Measure sensor resistance. If the resistance is too low, the sensor has short-circuited. If the resistance is not consistent with the sensors resistance
characteristics table, the sensor has failed. Refer to Table 6-3.1 in Part 6, 3.1 Temperature Sensor Resistance Characteristics”.