Midea V6 Series Service Manual
2.17 H8: High pressure sensor error
Digital display output
Description
High pressure sensor error.
All units stop running.
Error code is only displayed on the unit with the error.
Trigger / recover condition
Trigger condition: Discharge pressure 0.3MPa.
Recover condition: Discharge pressure > 0.3MPa.
Reset method: Resume automatically.
Possible causes
Pressure sensor not connected properly or has malfunctioned.
Insufficient refrigerant.
Low pressure side blockage.
Poor evaporator heat exchange.
Main PCB damaged.