V6 VRF 50/60Hz
100
Midea V6 Series Service Manual
The specific error codes xL0, xL1, xL2 and xL4 can also be obtained from the inverter module LED indicators. If an inverter
module error has occurred, LED2 is continuously on and LED1 flashes.
Figure 6-2.4: LED indicators LED1 and LED2 on inverter module
Table 5-3.2: Errors indicated on LED1
LED1 flashing pattern Corresponding error
Flashes 8 times and stops for 1 second, then repeats xL0 - Inverter module protection
Flashes 9 times and stops for 1 second, then repeats xL1 - DC bus low voltage protection
Flashes 10 times and stops for 1 second, then repeats xL2 - DC bus high voltage protection
Flashes 12 times and stops for 1 second, then repeats xL4 - MCE error