AiRanger XPL Plus
Technology based. Customer driven.
October 1997
Instruction Manual
PL-532
33455320
Rev 2.2

Questions and Answers

  • J
    Jack RivasAug 27, 2025
    What to do if Milltronics Control Unit reading is fixed?
    • R
      Robert HaleAug 27, 2025
      If the reading is fixed, regardless of the actual material level, the transducer beam may be obstructed, the standpipe is too narrow, or the transducer mounting is resonant. Relocate and / or reaim transducer at material level or object.
  • E
    Erica CastroAug 27, 2025
    What to do if my Milltronics Control Unit always reports the material level 'off'?
    • T
      todd62Aug 27, 2025
      If the material level reported is always 'off' by the same amount, the empty (zero) reference is incorrect. You should check Empty (P006), Reading Offset (P063), Offset Calibration (P650), & Offset Correction (P652).
  • M
    middletonstacieAug 25, 2025
    What to do if Milltronics Control Unit displays 'EEEE'?
    • R
      Rachel ReillyAug 26, 2025
      If the Milltronics Control Unit displays 'EEEE', it means the reading is too high. To resolve this, select larger units (P005) or lower the Convert Reading value (P061).
  • M
    Michelle AndersonAug 23, 2025
    What to do if Milltronics Control Unit reading is erratic?
    • J
      jgrayAug 25, 2025
      If the reading is erratic with little or no relation to the material level, the true echo may be too weak or the wrong echo is being processed. Try to relocate and / or reaim transducer at material level or object.

Summary

Installation

Location, Mounting, and Cable Entry

Covers ideal mounting locations, physical mounting, and cable entry requirements.

Programming

Entering Program Mode and Value Alteration

Steps to enter programming and change parameter values.

Quick Start Parameters

Initial Configuration Settings

Sets up operation mode, material, response, transducer, units, empty, and span.

Operation

Performance Evaluation and Testing

Steps to verify system performance and complete setup.

Application Parameters

Reading and Failsafe Configuration

Adjusts reading display and configures failsafe behavior.

Relay Configuration

Sets up relay alarms and setpoints.

mA Output Configuration

Configures mA outputs and their limits.

Enhancement Parameters

Troubleshooting Guide

Symptoms, Causes, and Actions

A table listing common issues and solutions.

Measurement Difficulties and LOE Display

Troubleshooting common measurement problems and the LOE indicator.

Fixed and Wrong Readings

Diagnosing and resolving fixed or incorrect readings.

Milltronics airanger XPL plus Specifications

General IconGeneral
ManufacturerSiemens
TypeUltrasonic Level Transmitter
Frequency50 kHz
Process PressureUp to 3 bar
Accuracy± 0.25% of range or 6 mm (0.25 inch), whichever is greater
Process Temperature-40 to +85 °C (-40 to +185 °F)
CommunicationHART
Beam Divergence10°
Output4-20 mA
Weight1.5 kg
Operating Temperature-40 to +80 °C (-40 to +176 °F)