3.1.4 PR 5220/04 DeviceNet
Additionally to the PR 5220/00 this instrument has a DeviceNet connection.
3.1.5 PR 5220/06 ProNet I/O
In addition to PR 5220/00, the instrument is provided with two ProNet I/O ports.
3.1.6 PR 5220/07 EtherNet IP
In addition to PR 5220/00, the instrument is provided with EtherNet-IP ports.
3.2 General information
The device contains two applications:
- Standard
- EasyFill
Most functions are supported by both applications.
Some functions depend on the application.
3.3 Overview of the device
- Precision 10.000 e according to OIML R76
- Internal resolution 7.5 million counter steps
- Linearity <0.002%
- Measure rate is congurable: 6100/sec
- Digital lter with adjustable characteristic line
- Electrically isolated interfaces
- 3 programmable pairs of limits
- 24 V DC supply voltage connection
- Connection via plug-in terminal blocks
- Socket for LAN adapter
- The device is snapped to a mounting rail.
- 5 Status LEDs for power supply, communication, error detection
- The "EasyFill" application allows for quick and reliable lling and emptying of
containers (for functional description, see Chapter 6.1).
The menu-guided calibration and conguration of the device are carried out on a
notebook/PC.
- Calibration using weights according to the mV/V method or using load cell data
(smart calibration)
- Analog output 0/420 mA, congurable for gross/net weight
- Analog value via eldbus
- 3 digital inputs, electrically isolated
- 3 digital outputs, electrically isolated