Command Mode - Configuration & Operation
36
OPERATION MENU/9. AFTER HOURS
This operation allows to manually set the daytime or the night time mode of operation thus over-riding the current
daytime or nighttime mode. The user is prompted for confirmation as shown below
After the confirmation the user is prompted to enter which mode to be set
After the user selection and information message is displayed that the daytime nighttime mode is updated.
OPERATION MENU/10. CLEAR VERIFY COUNT
This operation is used to clear all the verification counts accumulated during the alarm verification process. The
user is prompted for confirmation as shown below
After the confirmation the verification count is cleared and the information message is displayed that the counts are
cleared.
OPERATION MENU/11. EXIT
Exit to the main command menu.
Reports
Overview
Reports can be generated in command mode from the reports menu. Reports are shown on the shared LCD display
in a special format.
Alarm Log
The alarm log report displays the contents of the alarm event log on the shared display which contains the last 400
of any of the following events:
• activation of any alarm input or common control which activates the common alarm sequence
• activation of system reset
• clearing of the event log (as the first entry)
Each entry contains the time and date of the event and a description of what the event was, for example:
For input circuits the first line shows the programmed message, the second line shows the status of the circuit and
the position of the event in the queue along with the total number of events in the queue.
Manual night mode
Change ?Y/N
Select mode
1. Daytime
2. Night time
Day/night mode
updated
Clear all verif
Counters ?Y/N
Verify
Counters cleared
Nverf alm ipt
Active 002/016